Pressurized deaerator for steam boilers.
Capacity: from 1000 to 16000 liters
- Pressurized deaerator tank, necessary for a thermal full deaeration of the feed water.
- Best working conditions (temperature 105°C and internal pressure about 0.4 bar) are electronically controlled and managed.
- The steam, necessary to remove the dissolved gases in the water, is introduced through injectors positioned in the lower part of the reservoir and, through a modulating valve, in the degassing tower as well.
- Execution in horizontal cylindrical shape, with convex end-plates, and mounted on a stable steel support device designed for installing at proper height to avoid the cavitation phenomenon.
- Complete with an electronic water level management system and related alarms (low and high levels).
- Insulated with high-density rockwool and covered with embossed aluminum foil.
NOTE: The pressurized deaeration must always be coupled with a chemical deaeration.
Standard-production equipment:
- Steam injection system
- Magnetic level indicator
- Probes for water level control
- Inlet water line with pneumatic valve and filter
- Condensate return inlet
- Air vent
- Overflow
- Drain
- Thermometer
- Pressure gauge
- Safety valve
- Degassed hot water supply to boiler
- Board panel IP55
- Piping excluded, possible supply on request